Generador Diésel de 692.0 – 2,019.0 kW
HTW
Powered by MITSUBISHI
Generador Diésel de 625.0 – 3,108.0 kW
HMW
Powered by MTU

HTW
HMW
HTW
PLANTA ELECTRICA MITSUBISHI | Consumo Combustible Lt/Hr 75% carga | AMP STBY POWER | Fichas Técnicas | |||||
Modelo | KW | Modelo | 220 | 440 | ||||
PRP (1) | STBY (2) | Estándar | Contenedor | |||||
HTW-775 | 692.0 | 773.0 | S12A2 PTA | 144.36 | 2,539 | 1,269 | ||
HTW-870 | 789.0 | 868.0 | S12A2 PTA2 | 168.00 | 2,851 | 1,425 | ||
HTW-1025 | 933.0 | 1,025.0 | S12H PTA | 184.81 | 3,366 | 1,683 | ||
HTW-1215 | 1,089.0 | 1,210.0 | S12R PTA | 219.04 | 3,974 | 1,987 | ||
HTW-1350 | 1,227.0 | 1,348.0 | S12R PTA2 | 252.45 | 4,427 | 2,214 | ||
HTW-1525 | 1,380.0 | 1,521.0 | S12R PTAA2 | 270.30 | 4,995 | 2,498 | ||
HTW-1620 | 1,469.0 | 1,620.0 | S16R PTA | 283.11 | 5,321 | 2,660 | ||
HTW-1825 | 1,654.0 | 1,820.0 | S16R PTA2 | 333.49 | 5,977 | 2,989 | ||
HTW-2020 | 1,821.0 | 2,019.0 | S16RPTAA2 | 357.36 | 6,631 | 3,315 |
HMW
PLANTA ELECTRICA MTU | Consumo Combustible Lt/Hr 75% carga | AMP STBY POWER | Fichas Técnicas | |||||
Modelo | KW | Modelo | 220 | 440 | ||||
PRP (1) | STBY (2) | Estándar | Contenedor | |||||
HMW-695 T6 | 625.0 | 692.0 | 12V2000G85 | 128.01 | 2,273 | 1,136 | ||
HMW-785 T6 | 711.0 | 785.0 | 16V2000G45 | 142.69 | 2,578 | 1,289 | ||
HMW-810 T6 | 736.0 | 809.0 | 16V2000G85 | 148.34 | 2,657 | 1,328 | ||
HMW-875 T6 | 794.0 | 870.0 | 18V2000G85 | 156.63 | 2,857 | 1,429 | ||
HMW-915 T6 | 829.0 | 915.0 | 12V4000G43 | 167.57 | 3,005 | 1,503 | ||
HMW-975 T6 | 879.0 | 972.0 | 12V4000G83 | 180.16 | 3,192 | 1,596 | ||
HMW-1020 T6 | 920.0 | 1,015.0 | 16V4000G43 | 184.09 | 3,334 | 1,667 | ||
HMW-1205 T6 | 1,092.0 | 1,203.0 | 16V4000G83 | 217.08 | 3,951 | 1,975 | ||
HMW-1235 T6 | 1,119.0 | 16V4000G83 | 0 | 0 | ||||
HMW-1550 T6 | 1,402.0 | 1,546.0 | 16V4000G83 | 265.12 | 5,078 | 2,539 | ||
HMW-1730 T6 | 1,612.0 | 1,728.0 | 16V4000G83 | 301.28 | 5,675 | 2,838 | ||
HMW-1975 T6 | 1,840.0 | 1,972.0 | 16V4000G83 | 357.61 | 6,477 | 3,238 | ||
HMW-2230 T6 | 2,080.0 | 2,228.0 | 16V4000G83 | 397.67 | 7,317 | 3,659 | ||
HMW-2520 T6 | 2,516.0 | 16V4000G83 | 685.00 | 8,263 | 4,132 | |||
HMW-2550 T6 | 2,312.0 | 2,548.0 | 16V4000G83 | 471.22 | 8,368 | 4,184 | ||
HMW-2820 T6 | 2,559.0 | 2,817.0 | 16V4000G83 | 516.40 | 9,252 | 4,626 | ||
HMW-3110 T6 | 2,824.0 | 3,108.0 | 16V4000G83 | 556.50 | 10,208 | 5,104 |
(1) P.R.P. Prime Power – ISO 8528: es la potencia máxima disponible para un ciclo de potencia variable que puede ocurrir por un número ilimitado de horas por año, entre periodos de mantemientos señalados . La potencia media consumible durante un periodo de 24 horas no debe rebasar el 80% de la P.R.P. 10% de sobrecarga es permitido solo por regulación
Standby power (ISO 3046 Fuel Stop pwer): es la potencia máxima disponible para empleo bajo cargas variables por número limitado de horas año (500h) dentro de los siguientes limites máximo de funcionamiento: 100% de carga 25h/año – 90% de la carga 200h/año. No existe sobrecarga. Es aplicable en caso de interrupción de la distribución en zonas de red eléctrica confiable.